◆ Environmental protection and safety upgrade: Emissions meet National VI/EU standards, standard sound insulation and explosion-proof design, comprehensive safety protection
◆ Advantages of high-voltage transmission: Output voltage ≥ 10kV, reducing long-distance transmission losses, can directly drive high-power equipment, and simplify the distribution system
◆ Intelligent and flexible configuration: integrated PLC control module, supports remote monitoring and multi-machine parallel connection, single machine capacity covers 500kVA-50MVA
◆ High efficiency and durability: Adopting technologies such as high-pressure common rail, the combustion efficiency is improved by 15%-20%, and the fuel consumption is low; high-strength components make the overhaul period reach 15,000-20,000 hours
1. Analysis and comparison of high-pressure diesel generator sets and low-pressure diesel generator sets
2. Relationship between power, voltage and current
P=1.732×U×I×COSΦ
Take a 2000kW unit as an example, power factor 0.8, frequency 50Hz low voltage (400V)
The current is: I = P / (1.732 × U × COSΦ) = 2000 × 103 / (1.732 × 400 × 0.8) = 3609A
High voltage (10.5KV)
The current is: I = P / (1.732 × U × COSΦ) = 2000 × 103 / (1.732 × 10.5 × 103 × 0.8) = 137A. The high-voltage transmission current is equivalent to 1/26 of the low-voltage transmission current.
3. Application of high voltage diesel generator sets
According to the application characteristics of the above-mentioned high and low voltage diesel generator sets, in applications with large capacity requirements and long power transmission distances, high-voltage diesel generator sets have obvious advantages such as large capacity, long-distance power supply, centralized construction of computer rooms, strong reliability, and simple supporting power distribution systems. They are an inevitable trend in the selection and application of large-capacity units. High-voltage diesel generator sets have been widely used in banks, data centers, metallurgy, civil aviation and other fields.
The main voltage levels of 50Hz high-voltage diesel generator sets are: 6kV, 6.3kV, 6.6kV, 10kV, 10.5kV, 11kV, etc. The power of a single unit is generally above 1000kW, and multiple units are used in parallel.
4. Structural characteristics of high-voltage diesel generator sets
Online Inquiry